The Eco-mode control system from Rittal employs an intelligent strategy to effectively target the use of energy by disabling the internal fan when the temperature inside the enclosure falls to 10° K below the setpoint temperature. The fan is then enabled for a period of 30 seconds every 10 minutes to ensure the accuracy of the sensed temperature. When the temperature rises above 10° K below the setpoint, the fan is permanently enabled.
Rittal TopTherm air/water heat exchangers are equipped with the Eco-mode control system in order to minimise their energy consumption. TopTherm Generation ‘Blue e’ cooling units also benefit from the Eco-mode control system, which together with the use of energy efficient EC fan technology, provides increased energy savings.